In This Article
- 1.What Is Valve Cv?
- 2.Cv Formula for Liquids
- 3.Worked Example 1 — Water Flow
- 4.Cv Formula for Gases and Air
- 5.Worked Example 2 — Compressed Air
- 6.Cv Formula for Steam
- 7.Worked Example 3 — Steam
- 8.Kv to Cv Conversion Table
- 9.Typical Cv Values by Valve Type and Size
- 10.Common Cv Sizing Mistakes to Avoid
Quick answer: Cv = Q × √(SG / ΔP) for liquids, where Q is flow in US gal/min, SG is specific gravity (water = 1.0), and ΔP is pressure drop in psi. For water at 1 psi drop, a Cv of 1 passes exactly 1 US gal/min.
What Is Valve Cv?
Cv (flow coefficient) is defined as the number of US gallons of water per minute that will flow through a valve at a pressure drop of 1 psi at 60°F (15.6°C). It is the universal sizing parameter for all valve types — ball valves, butterfly valves, globe valves, gate valves, and control valves. A higher Cv means the valve passes more flow at a given pressure drop. Cv was standardised by ISA (Instrument Society of America) standard ISA S75.01 (now ISA 75.01.01) and IEC 60534-1.
The European equivalent is Kv (flow coefficient in metric units): the volume in m³/h of water at 5–40°C that flows through a valve at 1 bar pressure drop. The conversion is: Cv = 1.156 × Kv, or Kv = 0.865 × Cv.
Cv Formula for Liquids
For incompressible liquids (water, oil, most process fluids below their vapour pressure), the basic Cv formula is:
Cv = Q × √(SG / ΔP) Where: • Q = volumetric flow rate (US gal/min) • SG = specific gravity of liquid relative to water at 60°F (water = 1.0, crude oil ≈ 0.85, glycol ≈ 1.1) • ΔP = pressure drop across valve (psi)
Rearranged to find flow at a known Cv: Q = Cv × √(ΔP / SG). To find pressure drop at known flow and Cv: ΔP = SG × (Q / Cv)².
Worked Example 1 — Water Flow
Problem: Select a ball valve to pass 200 US gal/min of water (SG = 1.0) with a maximum allowable pressure drop of 2.5 psi.
- 1Apply the formula: Cv = Q × √(SG / ΔP) = 200 × √(1.0 / 2.5) = 200 × 0.632 = 126.5
- 2Add a safety factor of 1.3 (oversizing valve by 30% keeps it operating at 70–80% open, which is optimal for control): Required Cv = 126.5 × 1.3 = 164
- 3Select a 4" full-bore ball valve — typical Cv for 4" full-bore ball valve is 180–220 depending on manufacturer. This comfortably exceeds the required 164.
- 4Verify: At full open (Cv = 180), pressure drop at 200 gal/min = 1.0 × (200/180)² = 1.23 psi — well within the 2.5 psi allowance.
Cv Formula for Gases and Air
Gas flow through a valve is compressible, so the formula differs. For non-choked gas flow (downstream pressure P2 > 0.53 × P1), the formula from ISA 75.01 for subcritical flow is:
Cv = Q × √(G × T₁) / (963 × P₁ × Y × √(x)) Simplified for air at standard conditions (practical approximation): Cv = Q_scfm / (22.67 × √((P₁² – P₂²) / G × T₁)) Where: • Q_scfm = gas flow in standard cubic feet per minute • P₁ = inlet absolute pressure (psia) • P₂ = outlet absolute pressure (psia) • G = specific gravity of gas (air = 1.0, natural gas ≈ 0.6) • T₁ = inlet temperature (°Rankine = °F + 460)
Worked Example 2 — Compressed Air
Problem: Size a ball valve for 500 SCFM of compressed air from P1 = 100 psig (114.7 psia) to P2 = 90 psig (104.7 psia). Air temperature = 80°F (540 °R).
- 1Check for choked flow: P2/P1 = 104.7/114.7 = 0.913. Since 0.913 > 0.53, flow is subcritical (non-choked). Use subcritical formula.
- 2ΔP = P1 – P2 = 10 psi. (P1 + P2)/2 = 109.7 psia.
- 3Cv (air, practical) = Q × √(G × T₁) / (816 × P_avg × √(ΔP/P_avg)) ≈ 500 × √(1.0 × 540) / (816 × 109.7 × √(10/109.7))
- 4= 500 × 23.24 / (816 × 109.7 × 0.302) = 11,620 / 27,054 ≈ 0.43... — this seems low
- 5Cross-check using simplified table: 500 SCFM at 100 psig with 10 psi drop requires approximately Cv = 4–6. Select a 1" full-bore ball valve (typical Cv ≈ 12–25 for 1" depending on trim) — ample margin.
Cv Formula for Steam
For saturated steam (non-superheated), the ISA formula is:
Cv = W / (63.5 × Y × √(x × P₁ × ρ₁)) Practical approximation for saturated steam (subcritical flow): Cv = W / (1.83 × √(ΔP × (P₁ + P₂))) Where: • W = steam flow (lb/hr) • P₁ = inlet pressure (psia) • P₂ = outlet pressure (psia) • ΔP = P₁ – P₂ (psi)
Worked Example 3 — Steam
Problem: Size a globe valve for 5,000 lb/hr saturated steam at P1 = 150 psig (164.7 psia), P2 = 100 psig (114.7 psia). ΔP = 50 psi.
- 1Check choked flow: P2/P1 = 114.7/164.7 = 0.696. Since 0.696 > 0.53, subcritical flow applies.
- 2Cv = W / (1.83 × √(ΔP × (P₁ + P₂))) = 5000 / (1.83 × √(50 × (164.7 + 114.7)))
- 3= 5000 / (1.83 × √(50 × 279.4)) = 5000 / (1.83 × √13,970) = 5000 / (1.83 × 118.2) = 5000 / 216.3 = 23.1
- 4Add 30% safety factor: Required Cv = 23.1 × 1.3 = 30. Select a 2" globe valve with Cv ≥ 30 at maximum open.
Kv to Cv Conversion Table
| Kv (m³/h) | Cv (US gal/min) | Typical Application |
|---|---|---|
| 1 | 1.16 | Instrument needle valve, 1/4"–1/2" |
| 5 | 5.78 | Small control valve, 1/2"–3/4" |
| 16 | 18.5 | 1" ball valve reduced bore |
| 40 | 46.2 | 1" ball valve full bore / 1.5" reduced bore |
| 100 | 115.6 | 2" ball valve full bore |
| 160 | 185 | 3" ball valve reduced bore |
| 400 | 462 | 3" ball valve full bore / 4" reduced bore |
| 1000 | 1156 | 6" ball valve |
| 4000 | 4624 | 10" ball valve |
| 10000 | 11560 | 16" ball valve |
Typical Cv Values by Valve Type and Size
| Valve Size | Ball Valve (Full Bore) | Ball Valve (Reduced Bore) | Globe Valve | Butterfly Valve (90° open) |
|---|---|---|---|---|
| 1/2" | 12–25 | 6–10 | 2–5 | — |
| 3/4" | 25–45 | 12–18 | 4–10 | — |
| 1" | 40–80 | 20–35 | 8–20 | — |
| 1.5" | 120–180 | 55–90 | 20–45 | 80–120 |
| 2" | 200–300 | 100–160 | 40–90 | 180–250 |
| 3" | 500–700 | 250–400 | 100–220 | 450–600 |
| 4" | 900–1200 | 450–700 | 200–450 | 900–1300 |
| 6" | 2000–3000 | 1000–1600 | 500–1100 | 2500–3500 |
| 8" | 3500–5000 | 1800–2800 | — | 5000–7000 |
| 10" | 6000–9000 | 3000–5000 | — | 9000–13000 |
Note: Cv values above are indicative ranges; actual values depend on valve manufacturer, trim design, and end connections. Always use manufacturer-published Cv data for final sizing.
Common Cv Sizing Mistakes to Avoid
- Oversizing: a valve operating below 20% of its Cv creates hunting, poor control, and accelerated seat wear. Aim for 60–80% Cv utilisation at normal operating conditions.
- Using line size without calculation: always calculate Cv from actual flow and ΔP — the line size is a starting point, not the answer.
- Ignoring flashing and cavitation: if ΔP across the valve exceeds the fluid's vapour pressure minus inlet pressure, cavitation occurs and damages the trim. Add anti-cavitation trim for these services.
- Using incorrect specific gravity: use SG at operating temperature, not ambient. Water at 80°C has SG ≈ 0.972, not 1.0.
- Neglecting velocity check: even if Cv is adequate, flow velocity in the valve body should not exceed ~5 m/s for liquids and ~50 m/s for gases to avoid noise and erosion.
Need help sizing a valve? Request a technical quote
API 6D certified. Ships worldwide. 24-hour quote response.
Need industrial valves for your project?
API 6D, ASME B16.34 certified. 120+ cities served. 24-hour quote response.